Analogue Addressable Fire Panels FP1500 Manual for Installation, Configuration and Commissioning Version 2.1 / November 2003
FP1500 Installation, Configuration and Commissioning Manual 8 Figure 4. FP1500 main electronic board and connectors 1. Mains connector * 2. Transf
FP1500 Installation, Configuration and Commissioning Manual 9 available at this level. The installer may add and remove sensors, control events, pri
FP1500 Installation, Configuration and Commissioning Manual 10 3 INSTALLATION OF THE SYSTEM This chapter describes the installation process step by
FP1500 Installation, Configuration and Commissioning Manual 11 3.2 Panel positioning For optimum operation and maintenance of the fire panel, severa
FP1500 Installation, Configuration and Commissioning Manual 12 3.5 Electrical connections and cables The fire panel must be connected to the main
FP1500 Installation, Configuration and Commissioning Manual 13 For your safety, the order in which the power is reconnected must be: Mains first,
FP1500 Installation, Configuration and Commissioning Manual 14 3.5.2 Connections on the main electronic board Figure 9. FP1500 main board connect
FP1500 Installation, Configuration and Commissioning Manual 15 • Connect the output wires to points O+ and O- and the return wires to R+ and R-. Th
FP1500 Installation, Configuration and Commissioning Manual 16 If necessary, the fire panel has an auxiliary 24 VDC output. It a
FP1500 Installation, Configuration and Commissioning Manual 17 PG700 Portable unit for all types All sensors must be installed in clean environment
Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea © 2003 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V.
FP1500 Installation, Configuration and Commissioning Manual 18 External power supply 24 V power supply line from the fire panel Output auxiliary 24
FP1500 Installation, Configuration and Commissioning Manual 19 KAL 785/7013.5.7 Connecting relays Relays outputs can be connected to the correspon
FP1500 Installation, Configuration and Commissioning Manual 20 2. Check that the PINS on the IC are in good condition and unbent 3. Insert the IC
FP1500 Installation, Configuration and Commissioning Manual 21 4 SYSTEM CONFIGURATION The basic configuration of the system can be performed comple
FP1500 Installation, Configuration and Commissioning Manual 22 Figure 14. FP1500 keypad 4.1.1 General parameters The alphanumeric LCD screen of the
FP1500 Installation, Configuration and Commissioning Manual 23 checked. An alert is given if the detec
FP1500 Installation, Configuration and Commissioning Manual 24 In option 1 <Date> select: Day / Month / Year [DD/MM/YYYY] In option 2 <T
FP1500 Installation, Configuration and Commissioning Manual 25 If more detailed information is required about the type and address of each device
FP1500 Installation, Configuration and Commissioning Manual 26 4.1.5 Configuring elements [CONFIGURE] [# Exit] 1. System 4. System Op. 7. Events
FP1500 Installation, Configuration and Commissioning Manual 27 Element 001 is called [Write the name of the element] [Upper Case Letters and Number
FP1500 Installation, Configuration and Commissioning Manual 1 CONTENTS 1 Introduction...
FP1500 Installation, Configuration and Commissioning Manual 28 will use during the day period (e.g. 6:30 to 17:45). To change the alarm threshold
FP1500 Installation, Configuration and Commissioning Manual 29 [SYSTEM] [# Exit] 1. Loop 1 4. Loop 4 7. Sirens 2. Loop 2 5. Loop 5 8. Relays 3
FP1500 Installation, Configuration and Commissioning Manual 30 etc. After the allocated time, the siren changes to a continuous sound if one or mo
FP1500 Installation, Configuration and Commissioning Manual 31 [EVENTS] [# Exit] 1. General 2. Logical In option 1 <General Events> allo
FP1500 Installation, Configuration and Commissioning Manual 32 With Alert 1, the control unit warns of an alarm situation. The operator must press
FP1500 Installation, Configuration and Commissioning Manual 33 Resistor 150 Ohm Resistor 150 Ohm / ¼ WMaximum 1.2 Km MASTER SLAVE 4.2.3 Configurati
FP1500 Installation, Configuration and Commissioning Manual 34 [CONFIGURE] [# Exit] 1. System 4. System Op. 7. Events 2. See Config. 5. Check P
FP1500 Installation, Configuration and Commissioning Manual 35 LANGUAGE ADDRESS SPANISH ITALIAN PORTUGUESE ENGLISH Output to the next element
FP1500 Installation, Configuration and Commissioning Manual 36 Before starting the installation of the modem, check that no element i
FP1500 Installation, Configuration and Commissioning Manual 37 1<Options>: • Serial port: select the port where the modem is connected. •
FP1500 Installation, Configuration and Commissioning Manual 2 5.4.6 Supply faults ...
FP1500 Installation, Configuration and Commissioning Manual 38 baud, 8 data bits, 1 stop bit without parity. In the case of the US Robotics modem, t
FP1500 Installation, Configuration and Commissioning Manual 39 [Serial Port: [01] Activate Modem: [YES] 3. If you use the configuration soft
FP1500 Installation, Configuration and Commissioning Manual 40 For other applications using an ethernet network, contact your supplier. 4.2.7 Chan
FP1500 Installation, Configuration and Commissioning Manual 41 • Hardware flow control (As an external printer, the EPSON LX300 is recommended) To
FP1500 Installation, Configuration and Commissioning Manual 42 Press: <ENTER> The panel will indicates on what code number (between 01 and
FP1500 Installation, Configuration and Commissioning Manual 43 5 COMMISSIONING OF THE SYSTEM Finally, the analogue detection system has been instal
FP1500 Installation, Configuration and Commissioning Manual 44 • The general parameters are adjusted Choose language (See section 4.1) Standby
FP1500 Installation, Configuration and Commissioning Manual 45 • Disconnect half the installation and perform the auto-search. If the control unit
FP1500 Installation, Configuration and Commissioning Manual 46 5.4.5 Out of service The LED on the front of the control unit displays “Out of servi
FP1500 Installation, Configuration and Commissioning Manual 47 6 MAINTENANCE Fault repair and maintenance must be carried out by qualified personn
FP1500 Installation, Configuration and Commissioning Manual 3 1 INTRODUCTION The FP1500 Aritech analogue addressable fire detection system has been
FP1500 Installation, Configuration and Commissioning Manual 48 Batteries: Even though the batteries test OK, it is recommended they be changed every
FP1500 Installation, Configuration and Commissioning Manual 49 Replacing components All the components used in this control unit have been chosen t
FP1500 Installation, Configuration and Commissioning Manual 50 7 TECHNICAL SPECIFICATIONS Mechanical specifications: Enclosure 420 mm x 335 mm x 11
FP1500 Installation, Configuration and Commissioning Manual 51 Auxiliary 24 V output: Between 18 and 28 VDC, 250 mA; nominal 24 VDC Recommended
FP1500 Installation, Configuration and Commissioning Manual 52 Batteries: 2 units of 12 VDC 7 A/h (lead type) Alphanumeric screen: LCD screen
FP1500 Installation, Configuration and Commissioning Manual 53 8 APPLICABLE STANDARDS The FP1500 has been designed according to the EN54-2:1997 an
FP1500 Installation, Configuration and Commissioning Manual 54 9 APPENDIX: ADDRESSES OF MODULES 1 2 3 4 5 6 7 8 ON 128 1
FP1500 Installation, Configuration and Commissioning Manual 55 1 2 3 4 5 6 7 8ON2071 2 3 4 5 6 7 8ON20
FP1500 Installation, Configuration and Commissioning Manual 4 1.2 Glossary of symbols The symbols listed below appear throughout this manual to mak
FP1500 Installation, Configuration and Commissioning Manual 5 Figure 2. Basic diagram of the FP1500 analogue addressable fire detection system A
FP1500 Installation, Configuration and Commissioning Manual 6 • Disconnect the mains (110 VAC or 230 VAC) and the batteries before connecting or di
FP1500 Installation, Configuration and Commissioning Manual 7 2 THE FP1500 ANALOGUE FIRE PANEL 2.1 Description of the control panel This section pr